New FDNY rules for apartments, 3 RCNY §505-01/02 will assist first responders: Deadline is March 30th - By Evan Lipstein

February 05, 2018 - Owners Developers & Managers
Evan Lipstein,
Hyline Safety Company

3 RCNY §505-01/02 affects over 1 million apartments in NYC and building owners and managers must comply with the new rules or face potential violations issued by the FDNY.

The FDNY rule 3 RCNY §505-01 “Apartment and Guest Room Identification and Directional Markings and Signs” requires that apartment buildings have door numbers / letters marking all dwelling units for R-1 and R-2 buildings.

All apartment buildings must have the customary apartment number/letter door markings conspicuously positioned at eye-level between 48” – 60.” This portion of 3 RCNY §505-01 states that your building’s apartment doors must be properly marked with apartment numbers.

Under 3 RCNY §505-01 requires occupancies in Group R-1 and Group R-2 building with more than eight dwelling units on a floor have hallway corridor directional signs to aid emergency personnel in locating apartments when during fires, medical emergencies and other emergencies. The hallway corridor directional signs must be in conspicuous locations in the elevator lobby or other public entry on each floor, and opposite stairwell entrances.

The hallway corridor directional sign must have directional arrows with unit numbers / letters to direction to each unit. There are exceptions; hallway corridor directional signs are not required where all of units are located in a single direction from the elevator or stairwell entrance. If dwelling units are on more than one corridor, directional markings or signs must be placed at each place where the corridor intersects with another corridor. The hallway corridor directional signs must be between 48” – 60” above the floor. 

The FDNY’s second rule, 3 RCNY §505-02  “Apartment, Guest Room and Stairwell Fire Emergency Markings” requires new low-mounted marking of apartment entrance doors with emergency markings to help firefighting operations, improving safety for both firefighters and building occupants. The newly required fire emergency marking enables firefighters to find apartment numbers in smoke conditions that obscure normal eye-level door numbers.  Such identification ensures firefighters can quickly conduct search and rescue operations.

Additionally, new emergency markings for duplex and triplex apartments make it possible for firefighters to know what level of an apartment they’re entering, i.e., the upper level of a duplex apartment, where temperatures may be unsafe. The 3 RCNY §505-02 fire emergency markings also indicate when apartments have more than one door or are joined horizontally. The different apartment doors must be marked with a star or a triangle to show whether they are a main entrance or a secondary entrance.

The need for doors to be marked extends to entrance doors that are obstructed from inside by furniture or even when a door is sealed with sheetrock giving the appearance of an unobstructed entrance door in the public hallway. According to the FDNY depending upon fire conditions its possible that even a lawfully obstructed entrance could be the only or safest means of access to an apartment.

3 RCNY §505-02 also applies to stairwell doors.  Stairwell doors must be identified by placing a marking, no higher than 12” off the floor on the doorjamb on the hinged side of the stairwell door in the hall.  Some buildings are exempt from this requirement. If the building already has photoluminescent exit path markings or if the building is 100% protected throughout by a sprinkler system. 

Take immediate action to comply, as some of the deadlines are already past. The FDNY set different compliance deadlines for 3 RCNY §505-01/02. Duplexes and triplexes were to comply by March 30 of 2017; buildings with only single-level apartments need to comply by March 30, 2018.

3 RCNY §505-02 signs are not beautiful and have some owners unhappy. Many owners, managers and residents are complaining that the newly required signs clash with their building’s décor.  Under the new code only certain types of materials are permitted for the signs. One type is photoluminescent – which means glow in the dark; the other is retroreflective, a highly reflective material that reflects light back to its source. Neither is too pretty.

However, there is good news for the buildings looking to keep up aesthetics. Hyline Safety offers apartment and stair door signs in custom colors to match your hallway décor. The rule states that the markings characters must contrast with the background against which the characters are viewed so the markings background can be the color of the doorjamb itself just so long as the characters are plainly discernible and are photoluminescent or retroreflective.

Evan Lipstein is the president and owner of Hyline Safety Company, Manhattan, N.Y.

Thanks for Reading!
You've read 3 of your 3 guest articles
Register and get instant unlimited access to all of our articles online.

Sign up is quick, easy, & FREE.
Subscription Options
Already have an account? Login here
Tags:

Comments

Add Comment